Pressure Switches & Sensors
A/DP2-7 Low Differential Pressure Transmitter
The A-DP2 Series low Differential Pressure Transmitters are capable of sensing full scale ranges down to 0.1” of water column. Each pressure transmitter utilizes a high quality ceramic capacitive sensor to provide long term stability and performance.
The A-DP2 Series low Differential Pressure Transmitters are capable of sensing full scale ranges down to 0.1” of water column. Each pressure transmitter utilizes a high quality ceramic capacitive sensor to provide long term stability and performance. Transmitters have +/- 0.3% of full scale accuracy over the compensated temperature range and this is critical for optimizing building pressure. This transmitter units are capable of being field adjusted to a maximum of three additional spans by resetting the internal jumpers.
Features & Benefits:- Field Selectable Outputs of 0 to 5VDC, 0 to 10VDC, and 4 to 20 mA
- RoHS
Others
- Minimum Operating Ambient Temperature
- -10 degree Celsius
- 14 degree Fahrenheit
- Maximum Operating Ambient Temperature
- 140 degree Fahrenheit
- 60 degree Celsius
- Includes
- Conduit Adapter
Others
- Minimum Operating Ambient Temperature
- -10 degree Celsius
- 14 degree Fahrenheit
- Maximum Operating Ambient Temperature
- 140 degree Fahrenheit
- 60 degree Celsius
- Includes
- Conduit Adapter
- Minimum Operating Ambient Temperature : -10 degree Celsius|14 degree Fahrenheit
- Maximum Operating Ambient Temperature : 140 degree Fahrenheit|60 degree Celsius
- Includes : Conduit Adapter