The Gamewell-FCI Velocity® Series, Addressable Dual Monitor Module features two Style B, Class B initiating device circuits, each with an end-of-line resistor.
The Gamewell-FCI Velocity® Series, Addressable Dual Monitor Module features two Style B, Class B initiating device circuits, each with an end-of-line resistor. This module provides addresses for any device or group of devices connected to each circuit. Any alarm initiating devices with normally open (N.O.) dry contacts, such as heat detectors, 4-wire projected beam smoke detectors, 4-wire smoke detectors, water flow switches, tamper switches, manual stations, etc. may be installed in these circuits. The module is designed for installation in the signaling line circuit of any Gamewell-FCI addressable control panel.
Features & Benefits:- Includes a compact size allows easy installation
- Accommodates any normally open contact device
- UL Listed
- FM
- CSFM
Others
- Normal Input Current
- 750 µA
- Alarm Current
- 6.4 milliampere
- LED Current
- 0.0057 ampere
- Maximum Operating Humidity
- 93 Percentage
- End of Line Resistance
- 47 kO
- Maximum Operating Voltage
- 15 - 32 DC volt
- 15 VDC
- Supported Wiring Configuration
- Class B
- Number of Inputs
- 2
- Maximum IDC Wiring Resistance
- 1 500 Ohms
- Approved Location
- CSFM 7300-17030107
- FM 3023594
- ISO 9001 Certified
- MEA FDNY 227-03-E Vol IV
- UL 2572
- UL S1949 2572 for Mass Notification
Others
- Normal Input Current
- 750 µA
- Alarm Current
- 6.4 milliampere
- LED Current
- 0.0057 ampere
- Maximum Operating Humidity
- 93 Percentage
- End of Line Resistance
- 47 kO
- Maximum Operating Voltage
- 15 - 32 DC volt
- 15 VDC
- Supported Wiring Configuration
- Class B
- Number of Inputs
- 2
- Maximum IDC Wiring Resistance
- 1 500 Ohms
- Approved Location
- CSFM 7300-17030107
- FM 3023594
- ISO 9001 Certified
- MEA FDNY 227-03-E Vol IV
- UL 2572
- UL S1949 2572 for Mass Notification
- Normal Input Current : 750 µA
- Alarm Current : 6.4 milliampere
- LED Current : 0.0057 ampere
- Maximum Operating Humidity : 93 Percentage
- End of Line Resistance : 47 kO
- Maximum Operating Voltage : 15 - 32 DC volt|15 VDC
- Supported Wiring Configuration : Class B
- Number of Inputs : 2
- Maximum IDC Wiring Resistance : 1 500 Ohms
- Approved Location : CSFM 7300-17030107|FM 3023594|ISO 9001 Certified|MEA FDNY 227-03-E Vol IV|UL 2572|UL S1949 2572 for Mass Notification